Proposed Structural Five story plan
Typology: Schemes and Mind Maps
Uploaded on 10/08/2024
2 documents
1 / 14
This page cannot be seen from the preview
Don't miss anything!
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
M G
H
WATER TANK
HOUSEGUARD
K^ L
O
9
OLD PS
N
R
I
SHED
ORCHIDARIUM
WATER TANK OLD BUILDING
STAIRS
P
R
A
B
D
E
D
N
F
PP-7^ OP-
PP-4 PP-2 OP-
OP-
PP-5CPP-5B PP-5A
OP-
OP-
OP-3 OP-
OP-
PP-
PP-3^ PP-5D
PP-
23
O PP-
PROPOSED SIX (6)-STOREY TRAUMA CENTER BUILDING
OP- 2 (BRAIN, HEART, LUNG, KIDNEY) CENTER BUILDINGPROPOSED EIGHT (8)-STOREY MULTI-SPECIALTY
OP- PSYCHIATRIC COMPLEX BUILDINGPROPOSED FOUR (4)-STOREY W/ BASEMENT
OP- OUT-PATIENT DEPARTMENT BUILDINGPROPOSED & RENOVATION /EXPANSION OF
OP- MOLECULAR / PCR LABORATORY AND ISOLATION ROOMSPROPOSED TWO-STOREY W/ BASEMENT
OP- (BASEMENT AREA) FOR ISOLATION ROOMS FOR MERS COVPROPOSED RENOVATION OF I.D.B. BUILDING
OP- PROPOSED EXPANSION OF MOLECULAR LABORATORY BUILDING
OP- NUCLEAR MEDICINE DEPARTMENT
CONCRETE MIXING AND PLACEMENT MATERIAL SPECIFICATIONS GENERAL NOTES^ CONSTRUCTION NOTES
NOTES ON REINFORCEMENT 600 600 600
400
400
A'
A
D
REBAR DIAMETER
D
HOOK LENGTH
HOOK LENGTH
NOTES ON SPLICES
600mm MINIMUM^ 40 BAR DIAMETER
NOTES ON CONCRETE HOLLOW BLOCKS NOTES ON COLUMNS
400 HOOK
400 HOOK
HOOK 400
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
S-
1
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
5 000
8 550
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
S-
FOUNDATION PLAN
1
FOUNDATION REINFORCEMENT SCHEDULE BOTTOM BARS
ADDITIONAL 25mmØ X 2,000MM IN BETWEEN CONT. TRANSVERSE BARS ADDITIONAL 25mmØ X 2,000MM IN BETWEEN LONGITUDINAL BARS
FOUNDATION REINFORCEMENT SCHEDULE
2
A'
B' A'
B'
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
A'
B'
2 000
2 000
2 000
A'
B'
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A'
B'
2 000
2 000
A' B C C' D
2 3 4 5 6 7 8
7'
1'
4'
2 700 6 400 3 600 3 600 2 800
19 100
2 000 2 000 2 000 2 000
200 900
25 100
21 028
17 324 3 195
1 800
40 835
A
8
S
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
BASEMENT 2 FRAMING PLAN
1
2 700 6 400 3 600 3 600 2 800
19 100
3 600
2 400
6 000
6 000
2 800
3 200
6 000
6 550
2 800
3 050
39 350
S-
A' B C C' D
1 2 3 4 5 6 7 8
7'
1'
4'
A
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
S-5b
GROUND FLOOR FRAMING PLAN
1
1 2 3 4 5 6 7 8
7'
1'
4'
3 600
2 400
6 000
6 000
2 800
3 200
6 000
6 550
2 800
3 050
39 350
A'
2 700 6 400 3 600 3 600 2 800
19 100
A B C C' D
COREBELL (SEE DETAILS)
2 910
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
SECOND FLOOR FRAMING PLAN
1
S-5c
1 2 3 4 5 6 7 8
7'
1'
4'
3 600
2 400
6 000
6 000
2 800
3 200
6 000
6 550
2 800
3 050
39 350
A'
2 700 6 400 3 600 3 600 2 800
19 100
A B C C' D
COREBELL (SEE DETAILS)
BEAM SCHEDULE
1
10mmØ SPIRAL TIES SPA. @ 100mm 10-20mmØ VERT. BARS W/
600
6 000 (MINIMUM OR UNTIL REFUSAL)
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
MARK BEAM
WIDTH (B) (mm)
DEPTH (D) (mm)
R E I N F O R C E M E N T S
LEFT SUPPORT
(mm)^ BOTTOM
(mm) TOP^ RIGHT SUPPORT
(mm)^ BOTTOM
MID-SPAN (mm) TOP
BOTTOM (mm)
SECTION
ØBAR
(mm)TOP
STIRRUPS
MARK BEAM
WIDTH (B) (mm)
DEPTH (D) (mm)
R E I N F O R C E M E N T S
LEFT SUPPORT
(mm)^ BOTTOM
(mm) TOP^ RIGHT SUPPORT
(mm)^ BOTTOM
MID-SPAN (mm) TOP
BOTTOM (mm)
SECTION
ØBAR
(mm)TOP
STIRRUPS
GROUND FLOOR FIRST BASEMENT^ SECOND BASEMENT
THIRD FLOOR SECOND FLOOR
0 600
0 450
10mmØ SPIRAL TIES SPA. @ 100mm 10-20mmØ VERT. BARS W/
S-
PILE REINFORCEMENT DETAILS
S (^3)
PILE SECTION DETAILS
2
A B A A B A A
MID-SPAN SPLICE 40d AT
SPLICE 32d AT COLUMN
OR SUPPORT
0.25L
L
L
L
D
D
D 0.25L
0.25L D
D 0.25L
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments of other contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
(mm)
Ø12 @ 200mm EACH WAY
COLUMN SCHEDULE
1
SLAB REINFORCEMENT SCHEDULE
2
(mm)
SHEAR WALL SCHEDULE
3
THK=1.20MMFY=418 MPARIB TYPE STEEL DECK COMPOSITE DECK
L
L/
L/
L
L/4 L/
@ 125MM O.C. B.W. 12MMØ RSB BOTTOM BARS SPA.SPA. @ 125MM BARS WITH STANDARD HOOK PROVIDE Ø12MM ADDITIONAL TOPFRAMINGREINFORCED CONCRETECOMPOSITE DECK ON @ 125MM O.C. B.W. LONGITUDINAL BARS SPA. 12MMØ RSB BOTTOM
SPA. @ 125MM BARS WITH STANDARD HOOK PROVIDE Ø12MM ADDITIONAL TOP
12MMØ RSB BOTTOM
TRANSVERSE BARS SPA. @ 125MM O.C. B.W.
BEAM
S-
600
600
600
600
600
600
600
600
600
16 - Ø
600
600
16 - Ø
600
600
600
600
18 - Ø
400
400 12 - Ø
400
400
12 - Ø
400
400
8 - Ø
400
8 - Ø20 400
400
400 10 - Ø
600
200 8 - Ø
SLAB ON DECK TYPICAL DETAILS
4
4 000 4 000 4 000 4 000 4 000 4 000 4 000 1 000
2 000
SCALE ELEVATOR SHAFT SECTION
1: ELEVATOR SHAFT DETAIL
S 2
1:100MTS
900 MM THK SLAB
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
S-
75MM O.C. 12MMØ RSB SPACED @ 3-20MMØ RSB
250 250
3-20MMØ RSB
SPACED AT 200MM O.C.4-20MMØ RSB WITH 10MMØ TIES
600 RC COLUMN (C2)
6 000
600
250
BOLT 4- 16MMØ X 200MM
4- 16MMØ X 200MM BOLT RC COLUMN (C2)
600 VERIFY 250 250 VERIFY 4- 16MMØ X 200MM BOLT I-BEAM
600
6 000
600
COREBELL SECTION DETAILS
1
BEAM SCHEDULE SECTION 1 SECTION 3 SECTION 2
250
250
SPACED AT 200MM OC10MMØ STIRRUPS
2-20MMØ RSB 2-20MMØ RSB
1:20 MTS
0 900
8 550
5 000
25MMØ BTM BAR @150MM O.C.25MMØ BTM BAR @125MM O.C.
900 MM THK SLAB
8 550
5 000
25MMØ TOP BAR @200MM O.C.25MMØ TOP BAR @250MM O.C.
1:100MTS
0 900 1 000 1 000
BOTTOM OF ELEVATOR FOOTING
4 000
2 000 2 000
SPACED @ 300MM O.C.12MMØ TRANSVERSE TOP BAR 16MMØ TOP BAR SPACED @ 200MM O.C. 12MMØ AT NOSING
12MMØ TRANSVERSE BOTTOM BAR SPACED @ 300MM O.C. SPACED @ 200MM O.C. 16MMØ BOTTOM BAR
TYPICAL STAIRS REINFORCEMENT DETAIL
12MMØ SPACED @ 300MM O.C.
500
1 500
125
12MMØ RSB SPACED AT 125 O.C.12MMØ RSB SPACED AT 200 O.C. 12MMØ RSB SPACED AT 100 O.C. 12MMØ RSB SPACED AT 200 O.C.
6-25MMØ RSB 2-20MMØ RSB 6-25MMØ RSB 1@50MM, 5@100MM, REST@250MM10MMØ STIRRUPS SPACED:
RAMP DETAILS
3
1:50MTS
300
182
1 200 MAX
515
450
B
C
D
C'
0 900 VERIFY 0 450
2 026
8 574
3 575
10MMØ STIRRUPS SPACED:
1@50MM, 5@100MM, REST@250MM
6-20MMØ RSB MID BAR^ 6-25MMØ RSB TOP BAR
6-25MMØ RSB TOP BAR
1:100MTS
MAT FOOTING^ RC COLUMN
b-b
500 800
9 000
5 450
900
RETAINING WALL SECTION ELEVATION
150 O.C. UP TO 4500MM 28MMØ RSB SPACED @ 150 O.C. UP TO 4500MM 25MMØ RSB SPACED @ @ 200MM O.C. 2-20MMØ RSB SPACED 150 O.C. UP TO 9000MM 25MMØ RSB SPACED @ 150 O.C. UP TO 9000MM 20MMØ RSB SPACED @ 2-25MMØ RSB
BUILDING LINE
BSMT 2 FFL BSMT 1 FFL^ GROUND FLOOR FFL
450
RC GUTTER WITH COVER
Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33 Drawings and specifications and author of said documents.the written consent of the architect orexecuted partly or in whole, withoutprojects or buildings, whetheruse in the repetition of and for otheror make copies of said documents forunlawful for any person to duplicatemade is executed or not. It shall bewhether the object for which they areand documents of the architect,service, are the intellectual propertystamped or sealed, as instruments ofother contract documents duly signed, RA 9266 SECTION 33
LOCATION
Cordillera Administrative Region^ BGHMC Compound, Baguio City
Medical Center Chief II
Baguio General Hospital & Medical Center
Baguio General Hospital & Medical CenterOIC, Chief of Medical Professional Staff
Chief Administrative Officer, HOPSS
Baguio General Hospital & Medical Center
Engineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY
S-
B-G03 (SEE BEAM SCHEDULE)
450
575
1-1/2" X 1-1/2" X
(^4) " 1
1" XANGLE BAR (^16) " FLAT BAR 3
1" X 1" X(SPACED @ 30MM)
(^16) " ANGLE BAR 3
1" X (^16) " FLAT BAR ( 3
1-1/2" X 1-1/2" XSPACED @ 30MM)
(^4) " 1
ANGLE BAR
(^800500)
9 000
5 450
900
DRAINAGE GUTTER SECTION
BUILDING LINE
BSMT 2 FFL BSMT 1 FFL^ GROUND FLOOR FFL
575
W/ APPROPRIATE ARRANGEMENT PROVIDE SHEAR 12 MM Ø SHEAR BARNOTE:* PROVIDE MESH & GRAVEL @ INLET* STAGGERED PLACEMENTHORIZONTAL SPACING: 1500 MM VERTICAL SPACING: 1000 MM 75 MM Ø WEEP HOLE
PIPE SHEAR BAR
CATCH BASIN W/ COVER ROAD PAVEMENT
SLOPE
12" STORM RCP
VARIES (600 MM MIN) 500
SLOPE
VARIES (600MM MIN)
700500
100180
500
576
500
500
SECTION 4a
CATCH BASIN COVER
RC GUTTER W/ COVER DETAILS
CATCH BASIN WITH COVER DETAILS
350
@ 200MM O.C. E.W. 10MMØ RSB SPACED
SPA. @ 200mm O.C. B.W.^ REINFORCEMENT = 10mmØTHICKNESS = 100 MM^ RC WALL/SLAB^ 12" STORM RCPCATCH BASIN COVER
SPA. @ 200mm O.C. B.W. REINFORCEMENT = 10mmØTHICKNESS = 100 MM RC WALL/SLAB
1-1/2"x1-1/2"x
(^4) " 1
1"x ANGLE BAR (^16) " FLAT BAR 3 SPACED @ 30mm
1 000
RC GUTTER W/ COVER
1 000
BEAM (SEE SCHEDULE)
1B-G03 (SEE BEAM SCHEDULE)
MAT FOOTING (SEE DETAILS)