Fundamentals of Heat and Mass Transfer [Solutions]-Wiley (2011) (1).pdf
Typology: Study Guides, Projects, Research
1 / 2638
This page cannot be seen from the preview
Don't miss anything!
KNOWN: Thermal conductivity, thickness and temperature difference across a sheet of rigid extruded insulation.
FIND: (a) The heat flux through a 2 m × 2 m sheet of the insulation, and (b) The heat rate through the sheet.
SCHEMATIC:
ASSUMPTIONS: (1) One-dimensional conduction in the x-direction, (2) Steady-state conditions, (3) Constant properties.
ANALYSIS: From Equation 1.2 the heat flux is
1 2 x
dT T - T q = -k = k dx L
Solving,
" x
q = 0.029 × m K⋅ 0.02 m
x (^2)
q = 14. m
The heat rate is
2 x x (^2)
q = q A = 14.5 × 4 m = 58 W m
COMMENTS: (1) Be sure to keep in mind the important distinction between the heat flux (W/m^2 ) and the heat rate (W). (2) The direction of heat flow is from hot to cold. (3) Note that a temperature difference may be expressed in kelvins or degrees Celsius.
qcond
A = 4 m 2
T 1 T (^2)
k = 0.029 (^) ⋅
W m K
x
L = 20 mm
T 1 – T 2 = 10˚C
qcond
A = 4 m 2
T 1 T (^2)
k = 0.029 (^) ⋅
W m K
x
L = 20 mm
T 1 – T 2 = 10˚C
KNOWN: Thickness and thermal conductivity of a wall. Heat flux applied to one face and temperatures of both surfaces.
FIND: Whether steady-state conditions exist.
SCHEMATIC :
ASSUMPTIONS : (1) One-dimensional conduction, (2) Constant properties, (3) No internal energy generation.
ANALYSIS: Under steady-state conditions an energy balance on the control volume shown is
2 q in ′′ = q out ′′ = q cond ′′ = k T ( 1 (^) − T 2 ) / L = 12 W/m K(50 C⋅ ° − 30 C) / 0.01 m° =24,000 W/m
COMMENTS: If the same heat flux is maintained until steady-state conditions are reached, the steady-state temperature difference across the wall will be
Δ T = q L k ′′^ / = 20 W/m^2 × 0.01 m /12 W/m K⋅ =0.0167 K
which is much smaller than the specified temperature difference of 20°C.
q ” = 20 W/m^2
L = 10 mm
T 1 = 50°C k = 12 W/m·K
T 2 = 30°C
q ″cond
KNOWN: Dimensions, thermal conductivity and surface temperatures of a concrete slab. Efficiency of gas furnace and cost of natural gas.
FIND: Daily cost of heat loss.
SCHEMATIC:
ASSUMPTIONS: (1) Steady state, (2) One-dimensional conduction, (3) Constant properties.
ANALYSIS: The rate of heat loss by conduction through the slab is
q k LW 1.4 W / m K 11m 8 m 4312 W t 0.20 m
The daily cost of natural gas that must be combusted to compensate for the heat loss is
g d (^6) f
q C (^) 4312 W $0.02 / MJ C t 24 h / d 3600s / h $8.28 / d
COMMENTS: The loss could be reduced by installing a floor covering with a layer of insulation between it and the concrete.
KNOWN: Thermal conductivity and thickness of a wall. Heat flux through wall. Steady-state conditions.
FIND: Value of temperature gradient in K/m and in °C/m.
SCHEMATIC :
L = 20 mm
k = 2.3 W/m·K
q ” x = 10 W/m 2
x
ASSUMPTIONS : (1) One-dimensional conduction, (2) Constant properties.
ANALYSIS: Under steady-state conditions,
" (^) 10 W/m 2 4.35 K/m 4.35 C/m 2.3 W/m K
dT q x dx k
= − = − = − = − ° ⋅
Since the K units here represent a temperature difference , and since the temperature difference is the same in K and °C units, the temperature gradient value is the same in either units.
COMMENTS: A negative value of temperature gradient means that temperature is decreasing with increasing x , corresponding to a positive heat flux in the x -direction.
KNOWN: Inner and outer surface temperatures of a glass window of prescribed dimensions.
FIND: Heat loss through window.
SCHEMATIC:
ASSUMPTIONS: (1) One-dimensional conduction in the x-direction, (2) Steady-state conditions, (3) Constant properties.
ANALYSIS: Subject to the foregoing conditions the heat flux may be computed from Fourier’s law, Eq. 1.2.
q k L W 15-5^ C q 1. m K 0.005m q 2800 W/m.
Since the heat flux is uniform over the surface, the heat loss (rate) is
q = qx A
q = 2800 W / m^2 3m^2
COMMENTS: A linear temperature distribution exists in the glass for the prescribed conditions.
KNOWN: Net power output, average compressor and turbine temperatures, shaft dimensions and thermal conductivity.
FIND: (a) Comparison of the conduction rate through the shaft to the predicted net power output of the device, (b) Plot of the ratio of the shaft conduction heat rate to the anticipated net power output of the device over the range 0.005 m ≤ L ≤ 1 m and feasibility of a L = 0.005 m device.
SCHEMATIC :
ASSUMPTIONS : (1) Steady-state conditions, (2) Constant properties, (3) Net power output is proportional to the volume of the gas turbine.
PROPERTIES: Shaft (given): k = 40 W/m⋅K.
ANALYSIS: (a) The conduction through the shaft may be evaluated using Fourier’s law, yielding
( ) ( ) " (^ )^2 / 4 40W/m K(1000^ 400) C (70 10 3 m)^2 / 4 92.4W 1m
h c c
k T T q q A d L
π π − − ⋅ − ° = = = × =
The ratio of the conduction heat rate to the net power output is
6 6
92.4W 18.5 10 5 10 W
q r P
= = = ×^ − ×
(b) The volume of the turbine is proportional to L^3. Designating L (^) a = 1 m, d (^) a = 70 mm and Pa as the shaft length, shaft diameter, and net power output, respectively, in part (a),
d = d (^) a × ( L/La ); P = P (^) a × ( L/L (^) a )^3
and the ratio of the conduction heat rate to the net power output is
( ) (^) ( (^ ) ) 2 2 2
3 2
(^3 2 6 6 )
2 2
( ) ( ) ( ) " / 4^ /^ / 4^ / 4 ( / ) 40W/m K(1000 400) C (70 10 m) 1m / 5 10 W (^) 18.5 10 m =^4
h c h c h c c a^ a^ a^ a^ a a a
k T T k T T k T T q A d^ d L L^ d L^ P r L^ L P P (^) P L L L
L L
π π π
π (^) − −
− − − = = = =
⋅ − ° × × × (^) × =
Continued…
L = 1m
d = 70 mm
P = 5 MW
Compressor^ Turbine
Shaft
T (^) h = 1000 °C
T (^) c = 400 °C
Combustion chamber
L = 1m
d = 70 mm
P = 5 MW
Compressor^ Turbine
Shaft
T (^) h = 1000 °C
T (^) c = 400 °C
Combustion chamber
k = 40 W/m·K
KNOWN: Width, height, thickness and thermal conductivity of a single pane window and the air space of a double pane window. Representative winter surface temperatures of single pane and air space.
FIND: Heat loss through single and double pane windows.
SCHEMATIC:
ASSUMPTIONS: (1) One-dimensional conduction through glass or air, (2) Steady-state conditions, (3) Enclosed air of double pane window is stagnant (negligible buoyancy induced motion).
ANALYSIS: From Fourier’s law, the heat losses are
q (^) g k (^) g A 1.4 W/m K 2m 19, 600 W L 0.005m
o
q (^) a k Aa 0.024 2m 120 W L 0.010 m
o
COMMENTS: Losses associated with a single pane are unacceptable and would remain excessive, even if the thickness of the glass were doubled to match that of the air space. The principal advantage of the double pane construction resides with the low thermal conductivity of air (~ 60 times smaller than that of glass). For a fixed ambient outside air temperature, use of the double pane construction would also increase the surface temperature of the glass exposed to the room (inside) air.
KNOWN: Dimensions of freezer compartment. Inner and outer surface temperatures.
FIND: Thickness of styrofoam insulation needed to maintain heat load below prescribed value.
SCHEMATIC:
ASSUMPTIONS: (1) Perfectly insulated bottom, (2) One-dimensional conduction through 5
walls of area A = 4m
2 , (3) Steady-state conditions, (4) Constant properties.
ANALYSIS: Using Fourier’s law, Eq. 1.2, the heat rate is
q = q A = k
′′ ⋅ A (^) total
Solving for L and recognizing that Atotal = 5×W 2 , find
5 k T W q
5 0.03 W/m K 35 - (^) ( -10 (^) ) C (^) ( 4m ) L = 500 W
o
COMMENTS: The corners will cause local departures from one-dimensional conduction and a slightly larger heat loss.
KNOWN: Dimensions and thermal conductivity of food/beverage container. Inner and outer surface temperatures.
FIND: Heat flux through container wall and total heat load.
SCHEMATIC:
ASSUMPTIONS: (1) Steady-state conditions, (2) Negligible heat transfer through bottom wall, (3) Uniform surface temperatures and one-dimensional conduction through remaining walls.
ANALYSIS: From Fourier’s law, Eq. 1.2, the heat flux is
q k 16.6 W/m L 0.025 m
o
Since the flux is uniform over each of the five walls through which heat is transferred, the heat load is
COMMENTS: The corners and edges of the container create local departures from one-
dimensional conduction, which increase the heat load. However, for H, W 1 , W 2 >> L, the effect is negligible.
KNOWN: Masonry wall of known thermal conductivity has a heat rate which is 80% of that through a composite wall of prescribed thermal conductivity and thickness.
FIND: Thickness of masonry wall.
SCHEMATIC:
ASSUMPTIONS: (1) Both walls subjected to same surface temperatures, (2) One- dimensional conduction, (3) Steady-state conditions, (4) Constant properties.
ANALYSIS: For steady-state conditions, the conduction heat flux through a one- dimensional wall follows from Fourier’s law, Eq. 1.2,
q ′′ = k
where ΔT represents the difference in surface temperatures. Since ΔT is the same for both walls, it follows that
k k
q (^1 2) q
1 2
2 1
With the heat fluxes related as
q 1 ′′ = 0.8 q′′ 2
L = 100mm 0.75 W / m K 0.25 W / m K
1 = 375mm.
COMMENTS: Not knowing the temperature difference across the walls, we cannot find the value of the heat rate.
PROBLEM 1.14 (Cont.)
1 x 1
x 1
T(x 0) T q ln b c T a q c T ln b a
Therefore, the temperature distribution is given by
q q T ln ax b T ln b a a
x 1
q (^) b T ln a ax b
COMMENTS: Temperature distributions are not linear in many situations, such as when the thermal conductivity varies spatially or is a function of temperature. Non-linear temperature distributions may also evolve if internal energy generation occurs or non-steady conditions exist.
KNOWN: Thickness, diameter and inner surface temperature of bottom of pan used to boil water. Rate of heat transfer to the pan.
FIND: Outer surface temperature of pan for an aluminum and a copper bottom.
SCHEMATIC:
ASSUMPTIONS: (1) One-dimensional, steady-state conduction through bottom of pan.
ANALYSIS: From Fourier’s law, the rate of heat transfer by conduction through the bottom of the pan is
T 1 T 2 q kA L
Hence,
qL T 1 T 2 kA
Aluminum :
600W 0.005 m T 1 110 C 110.40 C 240 W/m K 0.0314 m^2
Copper :
600W 0.005 m T 1 110 C 110.24 C 390 W/m K 0.0314 m^2
COMMENTS: Although the temperature drop across the bottom is slightly larger for aluminum (due to its smaller thermal conductivity), it is sufficiently small to be negligible for both materials. To a good approximation, the bottom may be considered isothermal at T ≈ 110 °C, which is a desirable feature of pots and pans.
KNOWN: Heat flux and convection heat transfer coefficient for boiling water. Saturation temperature and convection heat transfer coefficient for boiling dielectric fluid.
FIND: Upper surface temperature of plate when water is boiling. Whether plan for minimizing surface temperature by using dielectric fluid will work.
SCHEMATIC :
T sat, d = 52°C
q " = 20 × 10 5 W/m 2
T sat, w = 100°C
h (^) w = 20,000 W/m 2 ·K h (^) d = 3,000 W/m 2 ·K
ASSUMPTIONS : Steady-state conditions.
PROPERTIES: T sat ,w = 100°C at p = 1 atm.
ANALYSIS: According to the problem statement, Newton’s law of cooling can be expressed for a boiling process as
q ′′ = h T ( (^) s − T sat)
Thus,
Ts = T sat (^) + q ′′/ h
When the fluid is water,
5 2 , sat, (^3 )
20 10 W/m / 100 C 200 C s w w w 20 10 W/m K T T q h ′′ × = + = ° + = ° × ⋅
When the dielectric fluid is used,
5 2 , sat, (^3 )
20 10 W/m / 52 C 719 C s d d d 3 10 W/m K T T q h × = + ′′ = ° + = ° × ⋅
COMMENTS: (1) Even though the dielectric fluid has a lower saturation temperature, this is more than offset by the lower heat transfer coefficient associated with the dielectric fluid. The surface temperature with the dielectric coolant exceeds the melting temperature of many metals such as aluminum and aluminum alloys. (2) Dielectric fluids are, however, employed in applications such as immersion cooling of electronic components, where an electrically-conducting fluid such as water could not be used.
KNOWN: Hand experiencing convection heat transfer with moving air and water.
FIND: Determine which condition feels colder. Contrast these results with a heat loss of 30 W/m^2 under normal room conditions.
SCHEMATIC:
ASSUMPTIONS: (1) Temperature is uniform over the hand’s surface, (2) Convection coefficient is uniform over the hand, and (3) Negligible radiation exchange between hand and surroundings in the case of air flow.
ANALYSIS: The hand will feel colder for the condition which results in the larger heat loss. The heat loss can be determined from Newton’s law of cooling, Eq. 1.3a, written as
For the air stream:
qair ′′^ = 40 W m 2 ⋅ K 30⎡⎣ − − ( 5 )⎤⎦ K =1, 400 W m^2 <
For the water stream:
qwater ′′ = 900 W m^2 ⋅ K 30 ( − 10 K) = 18, 000 W m^2 <
COMMENTS: The heat loss for the hand in the water stream is an order of magnitude larger than when in the air stream for the given temperature and convection coefficient conditions. In contrast, the heat loss in a normal room environment is only 30 W/m^2 which is a factor of 400 times less than the loss in the air stream. In the room environment, the hand would feel comfortable; in the air and water streams, as you probably know from experience, the hand would feel uncomfortably cold since the heat loss is excessively high.